46
LMT S E R I E S |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER | O I/L M T 10 0/ 2 0 0 - EN R E V. B
Menu: Process Alarm (continued)
Menu/Parameter
Value Range
Description
Process Alarm/Alarm Source
Alarm Source
Software, Hardware
Indicates from where alarms are set
Process Alarm/Alarm Mode/Failure Mode
High, Low
Sets which direction to drive current when in
alarm
Process Alarm/Alarm Mode/Low Alarm Current
Low Alarm Current
3.5 - 3.8 mA
Value of current set when in low alarm
Process Alarm/Alarm Mode/High Alarm Current
High Alarm Current
20.5 - 22 mA
Value of current set when in high alarm
Process Alarm/Process Alarm Limits/Level
Level
Low Low
Low
High
High High
Alarms set at different points of process range
for Level
Signal available via HMI and HART protocol
Process Alarm/Process Alarm
Limits/Distance Ullage
Distance/Ullage
Low Low
Low
High
High High
Alarms set at different points of process range
for Distance/Ullage
Signal available via HMI and HART protocol
Process Alarm/Process Alarm Limits/Interface
Interface
Low Low
Low
High
High High
Alarms set at different points of process range
for Interface. Only applicable in 2 Levels and 2
Levels with Temperature device configuration
Signal available via HMI and HART protocol
Process Alarm/Process Alarm
Limits/Temperature
Temperature
Low Low
Low
High
High High
Alarms set at different points of process range
for Temperature Only applicable if device
configuration has temperature
Signal available via HMI and HART protocol