47
LMT S E R I E S |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER | O I/L M T 10 0/ 2 0 0 - EN R E V. B
Menu: Calibrate
Level Calibration
Interface
Calibration
Process
Temperature
Calibration
Temperature Offset
Reset Calibration
Calibration Point
Reset Calibration
Calibration Point
Reset Calibration
PV URV
PV LRV
4-20mA D/A Trim
4 mA Trim
20 mA Trim
Current Simulation
Reset D/A Trim
Menu/Parameter
Value Range
Description
Level Calibration
Calibration Points
‘Out’ values range must be within 5% of the ‘In’
values range
SVL – Sensor value at Level
Points – Corresponds to points 00 and 01
In – Sensor value
Out – Level value
Reset Calibration
Resets calibration points to factory defaults
Interface Calibration
Calibration Points
‘Out’ values range must be within 5% of the ‘In’
values range
SVI – Sensor value at Interface
Points – Corresponds to points 00 and 01
In – Sensor value
Out – Level value
Reset Calibration
Resets calibration points to factory defaults
Process Temp Calibration
Temperature Offset
Reset Calibration
Resets calibration to factory defaults
4-20 mA D/A Trim
4 mA Trim
4 mA
Sets current to 4 mA
20 mA Trim
20 mA
Sets current to 20 mA
Current Simulatation
3.5-23.6 mA
Sets current to user defined value
Reset D/A Trim
Reset trim to factory defaults