12
1MRS 750741-MUM
Lon
Ç
/SPA Gateway
Installation Manual
SPA-ZC 100
4.
Technical data
Interfaces
- L
ON
W
ORKS
interface
type SPA-ZC 100 MM:
Optical glass fibre glass transmitter and
receiver with ST connectors
.
Optical fibre sizes to be used: 62.5/125
m
m
Emission Wavelength 820 nm
type SPA-ZC 100 BB:
Optical plastic fibre transmitter and receiver
with snap-in connectors.
max. communication rate 1.25 Mbits/s
- SPA-bus interface
RS-232, RS-485 or TTL
9-pin, male D-connector
max. cable length 0.5 m
max. communication rate 19200 bits/s
Dimensions
- BB
102 x 66 x 50
- MM
102 x 77 x 50
Weight
240 g
Power supply
Source
(via pins of the SPA-bus D-connector)
+8V DC from pin 9 (RS 485, TTL)
or +12V DC from pin 4 (RS 232C)
or +5V regulated DC from pin 8
Supply current consumption
- quiescent state
210 mA
- theoretical max.
390 mA
Environmental conditions
- service temperature
0...+55
o
C
- storage temperature
-40...+55
o
C
- max. relative humidity
95% (without condensation)