46
L ST 3 0 0 |
CO M PAC T U LT R A S O N I C L E V EL T R A N SM I T T ER | L S T 3 0 0 – EN R E V. E
Open channel flow on DTM
1
Click
Configuration
>
Device Setup
>
Basic Setting
.
2
Select
Flow
in the
Operate Mode
field and click
Set
.
3
Click
Configuration
>
Open Channel Flow
>
Open Channel
Selection
.
4
Select a value from the
Channel Shape
box and click
Apply
.
The
Triangular Notch Thin Plate Weir
is selected here as an
example .
5
The parameters and an image for the selected channel shape are displayed .
6
Complete the parameters and click
Calculate
.
7
The maximum flowrate is calculated and displayed at the top of the interface .
Note
The max flowrate calculation must be executed before the linearization table generation, to prevent an incorrect linearization
table .