L ST 3 0 0 |
CO M PAC T U LT R A S O N I C L E V EL T R A N SM I T T ER | L S T 3 0 0 – EN R E V. E
47
8
Click
Generate
to generate the linearization table for this channel shape .
9
The linearization table is displayed below .
10
Click
Store user curve to device
to store the linearization table to the device .
11
Click
Calibration
>
Linearization
>
Linearization
to confirm the setting .
12
Click
Load user curve from device
and select
Enable
in the
Linearization Status
field to active the open channel flow function .