Entity parameters for L2 display
Temperature
class – Gas
Temperature
class – Dust
Ambient
temperature
limitation
Input
Current
limitation
Voltage
limitation
Power limitation
Ci
Li
T4
T135 °C
-40 to 60 °C
100 mA
30 V
0.75 W
17 nF
10 uH
T4
T135 °C
-40 to 60 °C
160 mA
30 V
1 W
T5
T100 °C
-40 to 56 °C
100 mA
30 V
1.4 W
T6
T85 °C
-40 to 44 °C
50 mA
30 V
0.4 W
Entity parameters for L7 display
Temperature
class – Gas
Temperature
class – Dust
Ambient
temperature
limitation
Input
Current
limitation
Voltage
limitation
Power limitation
Ci
Li
T4
T135 °C
-40 to 85 °C
100 mA
30 V
0.75 W
13 nF
10 uH
T4
T135 °C
-40 to 70 °C
160 mA
30 V
1 W
T5
T100 °C
-40 to 40 °C
100 mA
30 V
1.4 W
T6
T85 °C
-40 to 40 °C
50 mA
30 V
0.4 W
Entity parameters for L0 display
Temperature
class – Gas
Temperature
class – Dust
Ambient
temperature
limitation
Input
Current
limitation
Voltage
limitation
Power limitation
Ci
Li
T4
T135 °C
-40 to 85 °C
100 mA
30 V
0.75 W
17 nF
10 uH
T4
T135 °C
-40 to 70 °C
160 mA
30 V
1 W
T5
T100 °C
-40 to 56 °C
100 mA
30 V
1.4 W
T6
T85 °C
-40 to 44 °C
50 mA
30 V
0.4 W
The devices must be installed in a protected environment in
accordance with the specific conditions on the test certificate .
Pollution degree 3 (refer to IEC 60664-1) must not be exceeded
for the macro environment of the device . The device conforms
to degree of protection IP66 / IP67 . If the device is installed as
intended, this requirement is met by the housing as standard .
When connected to the line supply, the electrical circuits must
not exceed overvoltage category III . When not connected to the
line supply, the electrical circuits must not exceed overvoltage
category II .
Meter design for NEPSI intrinsic safety,
ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20
Meter design for NEPSI combined C5 + C6, Ex protection code
is C7 .
Meter design for ATEX/IECEx combined E5 + E6, Ex protection
code is E7 .
Meter design for cFMus, combined F3 + F4, Ex protection code
is F8 .
IMPORTANT (NOTE)
For applications in US and Canada, when the temperature
under rated conditions is higher than 60 °C at the entry point or
60 °C at the branching point of conductors, accessories such as
cable, gland or conductors in conduit with minimum
temperature specification of 60 °C must be selected .
IMPORTANT (NOTE)
The devices may only be operated in explosive areas if the
housing covers have been fully closed .
WARNING
Static hazard clean only with a damp cloth .
Avertissement – Danger statique Nettoyez uniquement avec
un chiffon humide .
IMPORTANT (NOTE)
“C7” digit means that customers choose NEPSI Non Sparking or
Intrinsically Safe method of protection on the product .
Dedicated check box is to be marked by the manufacturer or
customers .
IMPORTANT (NOTE)
“E7” digit means that customers choose ATEX or IECEx Non
Sparking or Intrinsically Safe method of protection on the
product .
Dedicated check box is to be marked by the manufacturer or
customers .
Summary of Contents for LST300 Series
Page 26: ...26 LST300 COMPACT ULTR ASONIC LEVEL TR ANSMITTER LST300 EN REV E...
Page 27: ...LST300 COMPACT ULTR ASONIC LEVEL TR ANSMITTER LST300 EN REV E 27...
Page 28: ...28 LST300 COMPACT ULTR ASONIC LEVEL TR ANSMITTER LST300 EN REV E...
Page 59: ...LST300 COMPACT ULTR ASONIC LEVEL TR ANSMITTER LST300 EN REV E 59 Note...