CONFIGURATION PAGES
HMI MP53/MP56
1TNC928250M0201
40
4.4.1
FC610 device setting
This is the setting related to FC610 device which includes:
•
Communication parameters (baud rate, slave address etc.)
•
Display panel (LCD setting and password)
•
Real-time clock (RTC) time setting
Level 1
Level 2
Level 3
Value range
(PARA: Parameters)
(Conn:
Communication
setting)
(bAUd: Modbus
Baud Rate)
1200,2400,
4800,9600,
19200,38400,
57600,115200
(PArI: Parity Check)
None,ODD,EVEN
(CFd:
Communication
Failure Delay)
1-25 or 255
(Addr: Device
Address)
1-127
(OPT: Display Panel)
(CODE: Password
Setup)
The old password
0000-9999
(NEW: Input the new
code the first time)
0000-9999
(AGAIN: Input the new
code the second time)
0000-9999
(CODE: LCD Setting)
(Current display group)
ON/OFF
U_F
(Voltage and F display
group)
(3-9 display group)
(TSET: Time Setting)
(RTC: RTC TIME)
(NEW: Input the new
code the first time)
0000-9999
(AGAIN: Input the new
code the second time)
0000-9999
(dATE)
1-31
(HOUR)
0-23
(MINUTE)
0-59
(SECONd)
0-59