CONFIGURATIONS
INITIAL VALUES – IP CONFIGURATION
1TGC908004
35
—
7.
Configurations
7.1.
Initial Values – IP Configuration
Digital Gateway requires parameter settings as initial values for network operation. The pa-
rameters are required depending on Digital Gateway configuration. Additionally, parameter
for Web Server, OPC Server and Fieldbus are also required.
The parameters must be loaded onto the Compact Flash (CF) card using MNavigate tool be-
fore powering up. After successful communication between MNavigate and Digital Gateway
(either direct or via network) the parameters can then be changed from MNavigate through
the network.
Any change of communication related parameter for Ethernet network (e.g. IP
address) requires a restart of Digital Gateway. Fieldbus communication related pa-
rameter (e.g. comm. speed, or slave address) can be change during runtime of Digital
Gateway.
Parameter
Default Value
Range
Remarks
IP Address LAN 2 (LAN2)
192.168.200.100
Settings according to network
administrator
Subnet Mask LAN2
255.255.255.0
Settings according to network
administrator
Broadcast Address LAN2
192.168.200.255
Calculated automatically
Default Gateway LAN2
0.0.0.0
Settings according to network
administrator
IP Address LAN 1 (LAN1)
192.168.100.100
DCS / SCADA communication inter-
face:
Settings according to network
administrator
Subnet Mask LAN1
255.255.255.0
Settings according to network
administrator
Broadcast Address LAN1
192.168.200.255
Calculated automatically
Default Gateway LAN1
0.0.0.0
Settings according to network
administrator
IP Address LAN 3 (LAN3)
192.168.171.100
LAN 3 for field device connectivity
via Modbus TCP
Subnet Mask LAN3
255.255.255.0
LAN 3 is not used