DATA MAPPING
DEFAULT DATA MAP
1TGC908004
51
Modbus
Function
Code
Modbus
Register
Device
Number
Description
Remarks
2
11001
1
Stopped
1 = Motor Stopped or
Tripped or Feeder
open
2
11002
1
Runs
1 = Motor Runs or
Feeder closed
2
11003
1
CW or K1
1 = Motor Runs Clock-
wise
2
11004
1
CCW or K2
1 = Motor Runs Coun-
ter Clockwise
2
11005
1
Ready
1 = Off and Ready for
Operation. No
alarm/trip is available
2
11006
1
Alarm
1 = Any Alarm condi-
tion of protection or
supervision functions.
2
11007
1
New Trip
1 = Any Trip condition
of the protection or
supervision functions
2
11008
1
Test
1 = Main switch set to
test position. (Motor
cannot start)
2
11009
1
HW local
1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M10x
2
11010
1
Bus local
1 = Control Access is
passed to any control
station on the switch-
gear control network.
2
11011
1
Remote
1=Control Access is
passed to the Process
Control System
2
11012
1
DI0
1= Digital Input 0 of
M10x is on
Continued on the next page