DEFAULT DATA MAP
DATA MAPPING
60
1TGC908004
Switching Commands
The following table details the commands that are required from the Master (DCS / PLC) to
be sent to the M10x in order to control the motor or feeder module.
Operation
Type
Description
Modbus
Command
Remarks
Control Access
Remote control
0x2100
M10x is controlled via
DCS.
Bus-Local control
0x2104
DCS allows control via
local HMI.
Stop
Stop, Open
0x0201
Stops the M10x, Opens
contactor K1 for Con-
tactor Feeder applica-
tion
Start
Start CW
Close (CF)
Open (Act)
Start
Start Clockwise
Close for Contactor Feeder applica-
tion
Open for Actuator application
0x0202
Starts the M10x. Close
contactor K1
Start CCW
Close (Close)
Start Counterclockwise
Close for Actuator Application
0x0203
Start the M10x Coun-
terclockwise. Close
contactor K2.
Reset
Reset
0x1100
Reset of all trips
Table 29 Switching Commands sent from DCS to Digital Gateway