DIGITAL GATEWAY LED INDICATION
TROUBLESHOOTING AND MAINTENANCE
66
1TGC908004
LED indication
Description
Additional Information / Actions
Error in Digital Gate-
way XML
Configuration file
Possible cause could be an interrupted or
disturbed communication between
MNavigate and Digital Gateway while down-
loading.
Please use MNavigate to download the
Digital Gateway configuration again
Error in Digital Gate-
way XML
Parameter file
Possible cause could be an interrupted or
disturbed communication between
MNavigate and Digital Gateway while down-
loading.
Please use MNavigate to download the
Digital Gateway parameter again
Internal Digital Gate-
way error
Digital Gateway is not able to create inter-
nal database.
Please reboot the Digital Gateway
. If that
doesn’t resolve the
problem, use MNavi-
gate to download the Digital Gateway
configuration again.
XML file missing
During startup Digital Gateway is checking
if all required xml files are available. In case
of a missing file that error is indicated.
Please use MNavigate to download the
Digital Gateway configuration again.
Network configuration
error
Digital Gateway is not able to config-
ure the IP settings as mentioned in config-
uration file e.g. due to wrong setting of
Default Gateway parameter for that Ether-
net Interface.
Please use MNavigate to check the settings
and download the Digital Gateway configu-
ration again. If a download is not possible
please use a flash card reader (ref. to
MNavigate Help or MNavigate Manual).