REDUNDANCY
REDUNDANCY CONFIGURATION
1TGC908004
31
M10x Redundant Configuration
For
M10x-M
the parameter ‘Redundancy Disabled/Enabled’ must be set to ‘Enabled’ either
through MD panel on MNS / NeoGear module front or through MNavigate as shown in Table
8.
Note
: In case of M10x-TCP this setting remains ‘Disabled’.
MNavigate tool
MCUSetup tool
Table 8 M10x-M redundant communication setting
Digital Gateway Redundant Configuration
Configuration and Parameterization of MNS Digital [Upgrade] projects are done via MNavi-
gate tool.
The parameters must then be downloaded to both the Primary and Backup Digital Gateway
to become
effective.
In a project with multiple Digital Gateway most of the Digital Gateway parameter are identi-
cal. To ease the parameterization such parameters could be copied among the Digital Gate-
way
(Assign to Digital Gateway).
As Network address settings are different between the Digital Gateway
s if connected to the
same network those must be configured individually
The steps of configuring the redundant Digital Gateway is as following:
1. Set the Ethernet IP address of LAN1 and LAN2 for Primary and Backup Digital Gateway.
Figure 26 MNavigate IP address Parameterization for Primary and Backup Digital Gateway