REDUNDANCY CONFIGURATION
REDUNDANCY
32
1TGC908004
Network addresses must be set for both Primary and Backup Digital Gateway.
Table 9 Primary and Backup IP address setting
•
It is essential that the IP address setting for LAN 2 of Primary and Backup Digi-
tal Gateway
is different (e.g. Primary = 192.168.200.
100
/ Backup =
192.168.200.
101
).
•
The same subnet mask is used because both Ethernet ports are connected to
the same Ethernet network for MView
and MNavigate communication.
•
Digital Gateway
LAN3 is not used for M10x applications.
2.
Set the slave address for the selected Fieldbus / Field network interface.
Figure 27 MNavigate Fieldbus Slave address Parameterization for Primary and Backup Digital
Gateway