DATA MAPPING
DEFAULT DATA MAP
1TGC908004
55
Monitoring with Function Code 03 and 04
Monitoring of the measured (analogue) values from the individual M10x
is detailed in the fol-
lowing table.
Modbus
Function
Code
Modbus
Register
Device
Number
Modbus Register
Name
Format
Remarks
3
40001
1
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40002
1
Thermal image
Unsigned Int, 2
Byte
Used thermal
capacity (only
available if TOL
protection func-
tion is used)
3
40003
1
Time to trip
Unsigned Int,
2Byte
Time before M10x
will trip the motor
(only available if
TOL protection
function is used)
3
40004
1
Time to reset
Unsigned Int,
2Byte
Time required be-
fore reset allowed
(only available if
TOL protection
function is used)
3
40005
2
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40006
2
Thermal image
Unsigned Int,
2Byte
Used thermal
capacity
:
:
:
:
:
:
3
40509
128
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40510
128
Thermal image
Unsigned Int,
2Byte
Used thermal
capacity
3
40511
128
Time to trip
Unsigned Int,
2Byte
Time before M10x
will trip the motor
3
40512
128
Time to reset
Unsigned Int,
2Byte
Time required be-
fore reset allowed
Table 22 Default Modbus Map Measured Values of M10x
Summary of Contents for LVS Digital
Page 1: ... DISTRIBUTION SOLUTIONS LVS Digital with M10x Motor Controller Interface Manual Modbus ...
Page 6: ......
Page 8: ......
Page 78: ......
Page 80: ... Visit us http www abb com mns Document Number 1TGC908004 M0203 ...