10
M4M 30
NETWORK ANALYZER USER MANUAL
3.5.Technical data
Auxiliary power supply
Voltage range
[V]
48 to 240 VAC/VDC ±15%
Frequency
[Hz]
50/60 Hz ±5%
Power Consumption
[VA]
10 VA max
Installation category
CAT III 300V class per IEC 61010-1 edition 3
Protection fuse
T1 A - 277 VAC
Measurement accuracy*
Measurement type
True RMS up to the 40th harmonic
128 samples per cycle, zero blind
IEC 61557-12
IEC 61557-12 PMD/S/K70/0,5
Active energy
Class 0,5 acc. to IEC 61557-12
Class 0,5S acc. to IEC 62053-22
Reactive energy
Class 2 acc. to IEC 61557-12
Class 2S acc. to IEC 62053-23
Active power
Class 0,5 acc. to IEC 61557-12
Reactive power
Class 1 acc. to IEC 61557-12
Apparent power
Class 0,5 acc. to IEC 61557-12
Voltage
Class 0,2 acc. to IEC 61557-12
Current
Class 0,2 acc. to IEC 61557-12
Neutral current
Class 0,2 acc. to IEC 61557-12
Frequency
Class 0,1 acc. to IEC 61557-12
Unbalances
Class 0,2 acc. to IEC 61557-12
Harmonics, THD (Current, voltage)
Class 1 acc. to IEC 61557-12
*Accuracy referred to insertion with .../5A CT or Rogowski coils. Derating for .../1A CT.
Voltage measurement inputs
Measurement range
[V]
50 - 400 VAC (L-N) 87 - 690 VAC (L-L)
Measurement category
400V~ (CAT III)
Rated frequency
[Hz]
50-60 Hz
Max. VT secondary (indirect connection)
[V]
400 VAC (L-N)
Max over voltage
[V]
800 VAC (L-L)
Protection fuse
T1 A - 277 VAC
Current measurement inputs
Number of current inputs
4 (L1, L2, L3, N)
Indirect insertion with CT
CT secondary
5 A (Class 0.5S)
1 A (Class 1)
Measurement range without accuracy derating
50 mA - 6 A
Starting current
5 mA
Burden
0.024 VA at 6 A
Indirect insertion with Rogowski coils
(only M4M 30 Rogowski)
Rated current
10000 A
Measurement range without accuracy derating
100 A - 12 kA
Starting current
10 A