background image

Specifications 

Pickup: 

Accuracy: 
Curves: 

Burden: 

1.5-12.0A  in  0.25  amp  increments. 
0.3-2.4A  in  0.05  amp  increments. 
Instantaneous:  1-20  times 
pickup  in  0.1  increments 

For  other  ranges,  consult  factory. 

Time  pickup 

± 

3%;  Inst.  pickup 

± 

10% 

Switch  selectable  on  front  panel: 

Inverse 

Definite  Time 

Very  Inverse 

Long  Time  Inverse 

Extremely  Inverse  Long  Time  Very  Inverse 
Short  Time 

Long  Time  Ext.  Inverse 

Time  Dial  - adjustable  1-10 
in  increments  of  0.1 
Accuracy: 

± 

7%  or 

± 

1  cycle  whichever  is 

greater 
1.5-12A  unit:  2.8  VA  at  5A  (non-linear, 
see  IB) 

0.3-2.4A unit:  2.8  VA  at  1A  (non-linear, 

see  IB) 

Output Contact Rating: 

30  amperes tripping at  250  Vdc 
5  amperes continuous 

Series  Target 
Coil  Rating: 

Operating  Frequency: 
Control  Power  Drain: 
Temperature  Range: 
Transient  Immunity: 

Dielectric: 

Weight:  Micro-51 

Micro-511FT 

Volume:  Micro-51 

Micro-511FT 

August,  1991 

0.3  amperes  break  inductive  at  125  Vdc 

30  Amp  Tripping  (1 amp  minimum 
trip  circuit  current  req'd.  to  set  targets) 

For  trip  circuit  currents  below  1  amp,  .25 

amps minimum,  add  "_ST"  to  catalog  number 
for  sensitive  target  coil. 
50  Hz  or  60  Hz,  selectable  by  internal jumper 
Zero.  Unit  is  self-powered 
Minus  20°C  to  Plus  70°C 
More  than  2500V,  1 MHz  bursts  at  400  Hz 
repetition  rate  continuous  (ASNSI  C37.90.1 

SWC);  Fast  transient  test;  EMI  test. 
2000  Vac,  60  seconds 
all  circuits  to  ground 

Unboxed:  4.7  Ibs.  (2.1  kg) 

Boxed:  5.4  Ibs.  (2.3  kg) 

Unboxed:  7.8  Ibs.  (3.5 kg) 

Boxed:  9.6  Ibs.  (4.4  kg) 

0.26  cubic  feet 

0.48  cubic  feet 

Testing 

Conventional  overcurrent  relay  test  procedures 
using  commercially  available  test  sets  may  be 
used. 

How To  Order 

For  a  complete  listing  of  available  overcurrent 
relays  see  TO  41-025. 

To  place  an  order  or  for  further  information, 

contact  the nearest  District  Office. 

How To Specify 

Time  overcurrent  relays  shall  be  Asea  Brown 
Boveri  Type  Micro-51  Series.  Relay  shall  be 
microprocessor  based  with  eight  selectable 
curves,  self-powered,  self-checking,  and  of 
total  drawout  construction. 

Further Information 

List  Prices:  PL  41-020 
Technical  Data:  TO  41-025 

Instruction  Book:  IB 7.2.1.7-15<D 

Test  Plug:  IB 7.7.1.7-8<D 

Other  Protective  Relays: 

Application  Selector  Guide,  TO  41-016 

CD 

Available  upon  request,  only from  Allentown  Plant. 

Descriptive  Bulletin 

41-123M 

Page 3 

www 

. ElectricalPartManuals 

. com

Summary of Contents for MICRO-51

Page 1: ...ng Time Very Inverse Extremely Inverse Long Time Extremely Definite Time Inverse Short Time Inverse Wide current tap ranges with exceptional set ting resolution are offered 1 5 12A in 0 25A increments and 0 3 2 4A in 0 05A increments The time dial is adjustable from 1 to 10 in increments of 0 1 An instantaneous element is standard Instan taneous pickup is adjustable from 1 to 20 multi ples of the ...

Page 2: ...sh panel mounting_ The Flexitest switches provide ct shorting that allows the relay to be fully withdrawn from its case The switches and companion test plug allow tests to be performed to the relay in its case mounted in the panel 9697 06 05 3 92 1 f f eG TIME INST l i 15iti 3 1161099 TRI Al RM I TRIPBUS 1 I TYPICALFOR PHASES A B C AND NEUTRAL TRIPALARM Retrofit Kit The Micro 511FT design enables ...

Page 3: ...r for sensitive target coil 50 Hz or 60 Hz selectable by internal jumper Zero Unit is self powered Minus 20 C to Plus 70 C More than 2500V 1MHz bursts at 400 Hz repetition rate continuous ASNSI C37 90 1 SWC Fast transient test EMI test 2000 Vac 60 seconds all circuits to ground Unboxed 4 7 Ibs 2 1 kg Boxed 5 4 Ibs 2 3 kg Unboxed 7 8 Ibs 3 5 kg Boxed 9 6 Ibs 4 4 kg 0 26 cubic feet 0 48 cubic feet T...

Page 4: ...TAB TO REFR toi N USCD 158 DtA 1 85 101 0 5 1 QJTOUT Figure 4 Outline and Drilling Micro 51 in FT 11 Case T RI1IJrA fN f ITG ETAILS OR PRQJtq124 l ITe PILOT PLm 1ll INT ANl XU TOOTH t ttt tll U I lB 1Z SO IoI PROJ CTION t t RtJ JR tt EiT II ORID lED S T LY OR HIe L5 _ _ _ _ _ l 1 J1i 1 12 STUOS c _ S I OIR PFM l 16 28 DIf NSYONS IN IN t S D1I J1liIONS IN ILLJI I TERS I QUTLlI FI ID mILLING rOR REL...

Page 5: ... to catalog number Internal Connections 16D446A 10F446A Continuous Rating 4A _ 20A 4A 20A To place an order or for further information contact the nearest District Office Internal Connection Diagrams 16D446A Micro 51 Time Overcurrent Relay Drawout Test Case TA LDH IMPEDAN E SE IES TA GET tDIL Descriptive Bulletin 41 123M Page 5 CIRCUIT 8 SHIELD Gl Types MICRO 51 and MICRO 511FT Microprocessor Base...

Reviews: