3BSE083159
32
Section 3 Interface Modules
Type Tests and Environmental Conditions
Environmental
phenomena
Test
Description
Test levels
ESD
EN 61000-4-2
Enclosure contact ±6 kV
Enclosure air
±8 kV
RF field AM
modulated
IEC 61000-4-3
Enclosure
20 V/m 80% AM (1 kHz), 80–2700 MHz
10V/m 80% AM (1 kHz), 2700-6000 MHz
Fast transients
EN 61000-4-4
Power port
±2 kV
Signal ports
±2 kV
Surge
EN 61000-4-5
Power port
± 2 kV line to earth, ± 1 kV line to line
Signal ports
± 2 kV line to earth, ± 1 kV line to line
RF conducted
EN 61000-4-6
Power port
10 V 80% AM (1 kHz), 0.15–80 MHz
Signal ports
10 V 80% AM (1 kHz), 0.15–80 MHz
Power frequency
magnetic field
EN 61000-4-8
Enclosure
300 A/m 0, 16.7, 50, 60 Hz
Pulsed magnetic
field
EN 61000-4-9
Enclosure
300 A/m
Radiated emission
CISPR 16-2-3
Enclosure
Class B
ANSI C63.4
(FCC part 15)
Enclosure
Class B, 30 - 6500 MHz
Conducted
emission
CISPR 16-2-1 DC power ports
Telecommunication
ports Class B
Class B