background image

— 

I N S TA LL ATI O N  I N S TR U C TI O N S

OCB-1A

Connection block 

ABB Electrification Sweden AB

SE-721 61 Västerås

Sweden 

abb.com/lowvoltage

Further information:

Revision

B

Revision date 

2022-01-19

Document number

2TLC010076M0201

Page 2/2

© Copyright 2022 ABB.

All rights reserved. 

Specifications subject 

to change without notice.

10

28

118

4.5

73

34

39

33

54

FOR M4 INTERNAL HEX SCREW (4x)

13

24

Attach OCB to the surface using four M4 bolts. Connect the safety de-
vices to the M12 connectors and a blind plug to the unused connectors. 
Fasten the connectors (max tightening torque is 0.6 Nm).

Max voltage

30 V

Max current

2 A

Pollution degree

3

Overvoltage category

2

Protection class

IP67

Ambient temperature

-25…+80°C

Relative humidity

35 — 85 % (without icing or condensation)

Technical data

Connection example

Caution! All cable colors according to ABB standard cables.

Information for use in UK

Importer address

ABB Ltd

Tower Court, Coutaulds Way

Foleshill Enterprise Park,

Coventry

CV6 5NX,

United Kingdom

Conformity, UK

2012 No. 3032 – Restriction of the Use of Certain 
Hazardous Substances in Electrical and Electronic 
Equipment Regulations (RoHS)

Information for use in USA / Canada

For Use In Class 2 Circuits Only.
CAUTION: NOT FOR INTERRUPTING CURRENT.
ATTENTION: NE PAS UTILISER POUR COUPER LE COURANT.

Cable assemblies

Any listed CU (CYJV/7), 8-pin A-coding mating connector.

AWG

(mm

2

)

Ampere

22

(0.32)

2

24

(0.20)

2

26

(0.13)

1

28

(0.08)

0.8

30

(0.05)

0.5

Conductor size Maximum ampere ratings of the 

overcurrent protection:

Reviews: