4.4.6 Function test of General Stop
Performing the function test
Note
Action
Start the robot system.
1
The test is passed if the event message
90523 Safety Controller Protective Stop
triggered
appears in the event log.
Activate the General Stop.
2
If the event message
90523 Safety Control-
ler Protective Stop triggered
does not ap-
pear in the event log, then the test has
failed and the root cause of the failure must
be found.
Product manual - OmniCore E10
115
3HAC079399-001 Revision: C
© Copyright 2019-2022 ABB. All rights reserved.
4 Maintenance
4.4.6 Function test of General Stop