3.5.9 Configuring robot stopping functions
Introduction
The robot stopping functions, protective and emergency stop are configured using
the
Visual SafeMove
functionality in RobotStudio.
The protective stop function can be configured to be either an
Automatic Stop
(AS)
or a
General Stop
(GS). When the protective stop function is configured as
General
Stop
(GS), the activation of the protective stop device will initiate the protective
stop in any operating mode. When the protective stop function is configured as
Automatic Stop
(AS), the activation of the protective stop device will initiate the
protective stop in automatic mode only.
Note
It is not possible to configure both
Automatic Stop
and
General Stop
at the same
time on the OmniCore E10.
Note
The dedicated discrete safety input to activate the protective stop function can
be configured as either
Automatic Stop
(AS) or
General Stop
(GS). For
simultaneous use of AS and GS, support for a safety protocol is required. See
option SafeMove.
For more information about safety configurations, see
Application
manual - Functional safety and SafeMove
.
Configure the robot stopping functions in Visual SafeMove
WARNING
The new settings must be verified by test before the robot is used.
Continues on next page
96
Product manual - OmniCore E10
3HAC079399-001 Revision: C
© Copyright 2019-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.9 Configuring robot stopping functions
Summary of Contents for OmniCore E10
Page 1: ...ROBOTICS Product manual OmniCore E10 ...
Page 8: ...This page is intentionally left blank ...
Page 34: ...This page is intentionally left blank ...
Page 198: ...This page is intentionally left blank ...
Page 206: ...This page is intentionally left blank ...
Page 224: ...This page is intentionally left blank ...
Page 228: ......
Page 229: ......