Note/Illustration
Action
Location of wrist strap button:
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section
2
xx2100000318
Screws: Torx, countersunk screw M4x10 (4
pcs)
Insert the motor connector into the front
panel from inner side of the cabinet and
fasten it with the screws.
3
xx2100000813
Reconnect:
•
T4.X7, T4.X8, T4.X9, T4.X10,
T4.X11, T4.X12, T4.X15
•
X1 - K2.X7 & X22
•
PE.5 & PE.6
4
Secure the motor connector cables with
the velcro on the frame of the cabinet.
Tip
Use the same position as from removing
the motor connector.
5
Concluding procedure
Note/Illustration
Action
.
Close the door.
1
Continues on next page
312
Product manual - OmniCore V250XT
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
5 Repair
5.3.2.1 Replacing the motor connector
Continued