4.5.3 Function test of three-position enabling device
Performing the function test
Note
Action
Start the robot system and turn the mode
switch to manual mode.
1
This test is passed if the event message
10011 Motors ON state
appears in the
event log.
Press the three-position enabling device
to the middle position and then hold the
enabling device in this position.
2
If the event message
10011 Motors ON
state
does not appear, or if the event
message
20224 Enabling device conflict
appears in the event log, then the test has
failed and the root cause of the failure must
be found.
This test is passed if the event message
10012 safety guard stop state
appears in
the event log.
While still holding the three-position en-
abling device pressed, press the enabling
device harder to the enable the device's
third position.
3
If the event message
10012 Safety guard
stop state
does not appear, or if the event
message
20224 Enabling device conflict
appears in the event log, then the test has
failed and the root cause of the failure must
be found.
168
Product manual - OmniCore V250XT
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
4 Maintenance
4.5.3 Function test of three-position enabling device
Summary of Contents for OmniCore V250XT
Page 1: ...ROBOTICS Product manual OmniCore V250XT ...
Page 34: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 174: ...This page is intentionally left blank ...
Page 410: ...This page is intentionally left blank ...
Page 418: ...This page is intentionally left blank ...
Page 454: ......
Page 455: ......