11
D C S W I TC H D I S CO N N EC TO R S
Caution
Ensure cable suitability for
compression lugs and application
requirements. Use max. 2 pcs of
compression lugs per switch
terminal.
Warning
A minimum distance of 25,4 mm
(1 in) from current carried parts to
any conductive part.
Compression Lug dimensions
[ mm ]
A
: Maximum height
34
B
: Recommended maximum width
36
C
: Maximum length
105
D: Recommended bolt slot
10,5...14,3
Busbar width
[ mm / in ]
max
76,2 / 3
Minimum Busbar cross-section
acc. to UL98B
[
mm
2
]
800 A
1000 A
520
640
A
B
∅
D
C
—
Busbars and compression lugs