14
DC SWITCH DI SCON N EC TOR S
—
Mechanical lug kit
OZXA804
Caution
Always use counter torque when
tightening terminals!
Warning
A minimum distance of 25,4 mm
(1 in) from current carried parts
to any conductive part.
M12x25
54,2 Nm
480 lb.in
56,5 Nm
500 lb.in
Caution
Installation only as shown in
drawings.
4×
4×
Single lug cable cross section 2 x AWG
2-600 MCM.