13
AU TO M AT I C T R A N SFER S W I TC H , OT M _ C _ 2 1 D
3.5.3 OTM_C21D registers information
Register
Address
(DEC)
Function
code
(DEC)
Values
SWITCH I_STATUS
1
04
0=Open
1=Closed
SWITCH II_STATUS
2
04
0=Open
1=Closed
LN1_U1 VOLTAGE
3
04
Phase voltage for 2P/4P
Line Voltage for 3P
Voltage at 1V accuracy
(e.g. 230=230V)
LN1_U2 VOLTAGE
4
04
LN1_U3 VOLTAGE
5
04
LN2_U1 VOLTAGE
6
04
LN2_U2 VOLTAGE
7
04
LN2_U3 VOLTAGE
8
04
LN1_LINE_STATUS
9
04
0= Voltage OK
1= No voltage
2= Undervoltage
3= Overvoltage
4= Phase missing
LN2_LINE_STATUS
10
04
0= Voltage OK
1= No voltage
2= Undervoltage
3= Overvoltage
4= Phase missing
RATED_VOLTAGE
11
04
0=220/380V
1=230/400V
2=240/415V
UNDERVOLTAGE_THRESHOLD
12
04
5,10,15,20,25,30 %
OVERVOLTAGE_THRESHOLD
13
04
5,10,15,20,25,30 %
TRANSFER_DELAY_TS
14
04
0,1,2,3,5,10,15,20,25,30 s
RETURN_DELAY_TBS
15
04
0,5,10,20,30,60,120,300,600,900 s
Information of registers, values and access is
available in following table
Continued on next page