20
AUTOM ATI C TR A N S FE R SWITCH , OTM _C _ 21D
The 9-bit dip is used to control the switch for circuit testing, and the mismatch with
the load power supply will result in testing and transfer failure. Therefore, carefully
read this guide and set correct parameters based on the actual situation before using
this product.
Generator can not be used in no line priority. Keep generator setting “0” in this mode.
Table 7. Dip switch
The 9-bit dip switch is used to set the working
modes of transfer switch.
DIP
No.
Function
Setting
1, 2
Pole setting
01
10
11
00
2 poles
3 poles
4 poles
Invalid setting
3, 4
Mode setting
01
10
11 (Default)
00
No line priority
Manual back
switching
Line priority LN1
Invalid setting
5, 6
Voltage setting
01
10
11
00
240VAC/415VAC 230VAC/400VAC 220VAC/380VAC
Invalid setting
7
Frequency setting
0
1 (Default)
60Hz
50Hz
8
Generator selection 0
1 (Default)
No
Yes
9
Generator stop
delay setting
0
1 (Default)
240s
30s
Figure 15. Dip switch
—
4.4 Dip switch setting