96
PCS100 AVC-20
User Manual
11.2
Control Connections
PCS100 AVC-20 includes control connections for the need of local control or monitoring of the system.
Control connection terminals are located on Auxiliary Master Module at the bottom of the Master Controller
Enclosure.
11.2.1
Digital Inputs and Outputs
Digital input and output terminals are located on Auxiliary Master Module at the bottom of the Master Controller
Enclosure and numbered as shown in Figure 11-4 and explained in Table 11-2.
1
NC
2
C
3
NO
4
5
6
7
8
9
10
11
12
13
14
15
16
NC
C
NO
NC
C
NO
0 V
RUN
250 V
AC
/ 30 V
DC
1 A
WARNING
250 V
AC
/ 30 V
DC
1 A
FAULT
250 V
AC
/ 30 V
DC
1 A
TX ALARM
24 V
AC
/V
DC
, 1 A
START
0 V
STOP / RESET / INHIBIT
LOOP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
- +
NC
NC
Inhibit switch;
Located inside
inverter cabinet
door
(fitted at factory)
PCS100 AVC-20
200º C
C
us
to
m
er
M
on
it
or
in
g
an
d
A
lar
m
S
ys
te
m
s
Re
m
ot
e
C
on
tr
ol
Figure 11
-
3: Customer Terminals for Remote Control and Monitoring of PCS100 AVC
-
20
Terminal
Number
Description
Name
1
Relay output/250 V
AC
/30 V
DC
, 1 A/NC
RUN
2
Relay output/250 V
AC
/30 V
DC
, 1 A/C
RUN
3
Relay output/250 V
AC
/30 V
DC
, 1 A/NO
RUN
4
Relay output/250 V
AC
/30 V
DC
, 1 A/NC
WARNING
5
Relay output/250 V
AC
/30 V
DC
, 1 A/C
WARNING
6
Relay output/250 V
AC
/30 V
DC
, 1 A/NO
WARNING
7
Relay output/250 V
AC
/30 V
DC
, 1 A/NC
FAULT
8
Relay output/250 V
AC
/30 V
DC
, 1 A/C
FAULT
9
Relay output/250 V
AC
/30 V
DC
, 1 A/NO
FAULT