26
PositionMaster EDP300
DIGITAL POSITIONER | CI/EDP300-EN REV. D
… 6 Installation
… Electrical connections
Module for the emergency shutdown function*
When the 24 V DC signal is interrupted, the I/P module executes
the respective safety function, depending on the mechanical
construction.
The positioner output 1 is depressurized, and the valve is moved
to the safe position. In case of a double-acting actuator, output
2 is additionally pressurized.
The emergency shutdown module works independently of the
mother board, i.e., all information from the final control element
is available in the control system at any time.
Ter85
/
−
86
Supply voltage
24 V DC (20 to 30 V DC)
(electrically isolated from the input signal)
Safe position
Active at < 5 V DC
* There are two slots for the option modules. Any combination of different
option modules is possible. However, identical option modules cannot be
combined.
Limit switch
The limit switch can either be equipped with proximity switches
or with potential-free microswitches.
Limit switch Limit 1 / Limit 2 with proximity switches
Two proximity switches for independent position signaling.
Ter41
/
−
42, +51 /
−
52
Supply voltage
5 to 11 V DC
(Control circuit in accordance with DIN
19234/NAMUR)
Output ‘logical 0’
< 1.2 mA
Output ‘logical 1’
> 2.1 mA
Switching point
Adjustable between 0 and 100 %
Direction of action
Metal tag in proximity
switch
Metal tag outside
proximity switch
Type SJ2-SN (NC; log. 1)
< 1.2 mA
> 2.1 mA
Limit switch Limit 1 / Limit 2 with 24 V - microswitches
Terminals
41 / 42 / 43, 51 / 52 / 53
Supply voltage
maximum 24 V AC/DC
Load rating
Maximum 2 A
Change from two to one column
Summary of Contents for PositionMaster EDP300
Page 45: ...PositionMaster EDP300 DIGITAL POSITIONER CI EDP300 EN REV D 45...
Page 47: ...PositionMaster EDP300 DIGITAL POSITIONER CI EDP300 EN REV D 47...
Page 49: ...PositionMaster EDP300 DIGITAL POSITIONER CI EDP300 EN REV D 49...
Page 51: ...PositionMaster EDP300 DIGITAL POSITIONER CI EDP300 EN REV D 51 Note...