10.11.1 HEAT DISSIPATION PER UPS RANGE WITH NON-LINEAR LOAD
UPS Range
10kVA 15kVA 20kVA 25kVA 30kVA 40kVA 50kVA
Heat Dissipation with 100% Non-linear
Load per range (EN 62040-3)
W
600
900
1100
1400
1700
2300
2900
Heat Dissipation with 100% Non-linear
Load per range (EN 62040-3)
BTU/h
2048
3072
3754
4778
5802
7850
9898
Airflow (25° - 30°C) with 100% Non-
linear Load per range
(EN 62040-3)
m
3
/h
150
150
150
150
570
570
570
Heat Dissipation without load
W
120
150
150
170
250
300
350
10.12 BLOCK DIAGRAMS
10.12.1 WIRING AND BLOCK DIAGRAMS
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such
as a licensed service engineer from the manufacturer or from an agent certified by the manufacturer
10.12.2 RECOMMENDED CABLE SECTIONS & FUSE RATINGS
Cabinet A (10-15-20 kVA) & Cabinet B (10-15-20-25 kVA) terminal connections overview
Battery
(+ / N / - ) + PE
[quantity x mm
2
]
Input Rectifier
1L1, 1L2, 1L3 + N + PE
[quantity x mm
2
]
Input Bypass
2L1, 2L2, 2L3 + N + PE
[quantity x mm
2
]
Output load
3L1, 3L2, 3L3 + N + PE
[quantity x mm
2
]
Tightening Torque
[Nm]
4 x 16
5 x 16
5 x 16
5 x 16
1.5
+
N
-
PE
PE
1L1
1L2
1L3
N
2L1
2L2
2L3
N
3L1
3L2
3L3
N
PE
PE