04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Page 7/37 ABB
Modifications reserved
•
EN-IEC 60950-1
. IT equipment. Safety. Part 1: General requirements.
•
EN-IEC 62040-2
. Uninterruptible power supply (UPS). Part 2: EMC requirements.
The supplier’s responsibility is excluded in the event of any modification or intervention in the product by the
customer’s side.
Product Standards
Standards
Safety
IEC/EN 62040-1
IEC/EN 60950-1
Electromagnetic Compatibility
(EMC)
IEC/EN 62040-2 (C3)
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-2-2
Figure 1: Standards
1.4 Inquiries
Address inquiries about the UPS to the local office or agent authorized by the supplier. Please note the type
code and the serial number of the equipment and contact your nearest agent authorized by the supplier. The
serial number is shown in the nameplate of the product. For further information on troubleshooting, go to
Section 6.
1.5 Operation
Do not remove the enclosure of the UPS. This system is to be serviced by qualified service personnel only.
Do not disconnect the mains cable from the UPS or the building wiring socket during operation as this would
remove the ground to the UPS and of all connected loads.
In order to fully disconnect the UPS, press the OFF-button. Only after the UPS is shutdown, disconnect the
mains load.
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection with an
ampere rating in accordance with the IEC/EN 60934 standard or your local electrical code.
UPS
Breaker
6kVA
40 A
2-pole circuit breaker
10kVA
63 A
2-pole circuit breaker
Indiscriminate operation of switches may cause output loss or damage to equipment.
This UPS may be connected to a maximum of four External battery enclosures.
Do not dispose batteries on fire as they may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes.