22
A B B U PS PRODUC TS A N D SOLUTI ON S
03: Output frequency settings
Interface
Settings
Parameter 1:
Output frequency setting.
You may set the initial frequency on battery mode:
50:
output frequency is 50 Hz
60:
output frequency is 60 Hz
If converter mode is enabled, you may choose from the following output frequency:
50:
output frequency is 50 Hz
60:
output frequency is 60 Hz
%
%
%
BAT
T
LOA
D
H
z
—
04: ECO enable/disable
Interface
Settings
Parameter 1:
Output voltage
You may choose the following output voltage:
208:
output voltage is 208 Vac
220:
output voltage is 220 Vac
230:
output voltage is 230 Vac (default)
240:
output voltage is 240 Vac
05: ECO voltage range settings
Interface
Settings
Parameter 1:
Set the acceptable high voltage point and low voltage point for ECO mode
by pressing Down key or Up key
HLS:
High loss voltage in ECO mode in parameter 1.
The setting range in parameter 1 is from 5% to 10% of the nominal voltage.
(Default: 5%)
LLS:
Low loss voltage in ECO mode in parameter 1.
The setting range in parameter 1 is from -5% to -10% of the nominal voltage.
(Default: -5%)
5%
50
%
7
BAT
T
LOA
D
25
%
50%
75
%
100%
VAC
BAT
T
LOA
D
ECO
%
%
%
BAT
T
LOA
D
ECO
%
%
%
%
BAT
T
LOA
D
ECO
%
BAT
T
LOA
D
ECO
BAT
T
LOA
D
ECO
%