background image

9

3  I N S TA L L AT I O N

3 .2 .1  Planning before the installation

To ensure a long service life, install the unit 
in a position where any danger to the UPS 
is minimized:
•  Install the UPS indoors.
•  Leave enough space on each side of the cabinet 

to allow cooling airflow and ensure that the 
circulation of air to the ventilation slits is not 
obstructed.

•  Avoid excessively high temperatures and 

excessive moisture.

•  Make sure that the surface is solid and flat.

3 .2 .2  Positioning

PowerValue 11 RT G2 can be mounted in a rack 
or installed in a standalone configuration. 

WARNING

WATER CONDENSATION MAY OCCUR IF 
THE UPS IS UNPACKED IN A VERY LOW 
TEMPERATURE. TO AVOID HAZARDS AND 
RISK OF ELECTRIC SHOCK, WAIT UNTIL 
THE UPS IS FULLY DRY BOTH INSIDE AND 
OUTSIDE BEFORE INSTALLING/USING 
THE UPS.

WARNING

HANDLE THE UPS CAREFULLY TO AVOID 
INJURY FROM FALLING OBJECTS 
REFER TO THE TECHNICAL DATA SHEET 
FOR UPS WEIGHTS. 

3 .2 .3 

Rack-mount installation

WARNING

TO AVOID INJURY FROM FALLING OBJECTS 
MAKE SURE THAT THE RACK CABINET CAN 
ACCEPT THE UPS WEIGHT BEFORE 
INSTALLING IT, INCLUDING PROVISIONS 
FOR FIXING THE UPS BY SCREW.

IT IS RECOMMENDED TO INSTALL THE 
BATTERY STARTING FROM THE BOTTOM 
OF THE RACK

3 .2 .3 .1 UPS

Note that you need a rack-mounting kit 
(purchased separately) for this operation. This 
procedure is suitable for 19-inch rack cabinet 
installation with a minimum depth of 800 mm.
Identify the final position and keep 2U spacing 
for this installation. 

— 

3 .2  Site planning and positioning


3.2.1-1


3.2.1-3


3.2.1-2


3.2.1-1: 
Ear bracket


3.2.1-2:  
Rack rails


3.2.1-3:  
Rack-mount installation

WARNING

•  MAKE SURE THE MAINS SUPPLY AND THE TOTAL LOAD DEMAND ARE WITHIN UPS SPECIFICATIONS
•  THE UPS MUST BE POWERED FROM A SINGLE-PHASE GROUNDED WALL OUTLET, PROTECTED BY 

OVERCURRENT DEVICES ACCORDING TO LOCAL WIRING RULES (NOT APPLICABLE FOR POWERVALUE 11 
RT G2 3KVA S)

•  THE PLUG ON THE POWER SUPPLY CORD IS INTENDED TO SERVE AS THE DISCONNECT DEVICE, THE 

MAINS SOCKET OUTLET THAT SUPPLIES THE UPS SHALL BE INSTALLED NEAR THE UPS AND SHALL BE 

EASILY ACCESSIBLE (NOT APPLICABLE FOR POWERVALUE 11 RT G2 3KVA S)

•  AFTER REMOVING COVERS OVER BATTERY TERMINAL, STORE THEM SAFELY FOR FUTURE NEED. REMOVE 

SUCH COVERS ONLY IF IT IS INTENDED TO ATTACH A CONNECTOR TO A TERMINAL.

Summary of Contents for PowerValue 11 RT G2

Page 1: ...PowerValue 11 RT G2 1 3 kVA USER MANUAL PowerValue 11 RT G2 1 3 kVA...

Page 2: ...ent electrical hazard Failure to observe the related safety note may cause injury death or equipment damage This symbol in conjunction with the signal word WARNING indicates a potentially dangerous si...

Page 3: ...tallation 9 3 2 4 Standalone tower installation 11 3 2 5 PowerValue 11 RT G2 3kVA S installation 12 3 3 General characteristics 13 3 3 1 UPS front panel 13 3 3 2 UPS rear panel 13 4 Operation 15 4 1 C...

Page 4: ...rations DANGER DO NOT REMOVE ANY SCREWS FROM THE UPS SYSTEM OR FROM THE BATTERY CABINET DANGER OF ELECTRICAL SHOCK DANGER HIGH FAULT CURRENTS LEAKAGE CURRENTS BEFORE CONNECTING THE MAINS ENSURE THAT T...

Page 5: ...ES THE GROUND FROM THE UPS AND ALL CONNECTED LOADS NOTE PRESS THE OFF BUTTON TO FULLY DISCONNECT THE UPS ENSURE THE UPS IS ON BYPASS OR ON STANDBY MODE BEFORE DISCONNECTING IT FROM THE MAINS NOTE TO R...

Page 6: ...TTERIES IN A FIRE THE BATTERIES MAY EXPLODE WARNING DO NOT OPEN OR MUTILATE BATTERIES RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES IT MAY BE TOXIC DANGER COMPONENTS INSIDE THE UPS ARE CONNECTE...

Page 7: ...TIAL NEGATIVE EFFECTS ON HUMAN HEALTH AND THE ENVIRONMENT WHICH COULD OTHERWISE ARISE FROM INAPPROPRIATE WASTE HANDLING 2 1 2 For disposal in countries outside of the European Union THE CROSSED OUT WH...

Page 8: ...14 cable 1 x IEC C19 C20 cable only for 3KB 3KS 1 x external battery cable only for S models 1 x USB cable 1 x M16 cable gland only for 3KS model 1 x fixing plate for battery cable Rack mounting acces...

Page 9: ...E UPS WEIGHT BEFORE INSTALLING IT INCLUDING PROVISIONS FOR FIXING THE UPS BY SCREW IT IS RECOMMENDED TO INSTALL THE BATTERY STARTING FROM THE BOTTOM OF THE RACK 3 2 3 1 UPS Note that you need a rack m...

Page 10: ...ernal battery modules WARNING DO NOT PILE UPS AND EBM ENCLOSURES THEY MIGHT FALL OVER THE PICTURE BELOW REPRESENTS JUST A SIMPLIFIED CONNECTION DIAGRAM Identify the final position and keep 2U spacing...

Page 11: ...TO CHAPTER 4 6 TO ROTATE THE DISPLAY 3 2 4 1 UPS 1 Set up the stabilizer bracket then put the unit into the stabilizer bracket figure 3 2 4 1 1 NOTE PLEASE INSTALL THE 4 SCREWS TO ENSURE THAT THE UNIT...

Page 12: ...2 5 2 4 Pass the input cable through the gland assembly use PVC single cord 3G 2 5 mm2 double insulated rated 300 V IEC 60227 1 The overall diameter of the power supply cord must be approximately 10...

Page 13: ...front panel Figure 3 3 1 1 shows the front panel of the UPS 3 3 2 UPS rear panel The figures below show the connectors and ports in the UPS and external battery module rear panel 3 3 General character...

Page 14: ...S rear view 3 3 2 5 External battery module rear view RS232 AC output 10A AC input 16A EBM connector EPO Dry contact input port USB Port Dry contact output port AC output 16A SNMP AS400 slot 3 3 2 4 3...

Page 15: ...seconds to enter UPS self testing while in AC mode ECO mode or converter mode OFF Enter Button Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS UPS will be in standby...

Page 16: ...econds Low battery Buzzer beeps every second Bypass Beep every 10 minutes Overload Beep twice every second When powering on the LCD shows the UPS status The UPS will also return to this default screen...

Page 17: ...er bypass mode or bypass mode can be set from front panel Alarm sounds every 10 second Standby mode UPS is powered off and no output supply power but still can charge batteries Overload warning When t...

Page 18: ...WITCH ON THE LOADS ONE BY ONE AFTER THE UPS IS TURNED ON SWITCH OFF ALL OF THE CONNECTED LOADS BEFORE TURNING OFF THE UPS NOTE THE FIRST TIME THE UPS IS STARTED UP IT MUST BE CONNECTED TO THE UTILITY...

Page 19: ...Charger fail FU Bypass frequency unstable EE EEPROM error TON Input dry contact UPS turn on TOF Input dry contact UPS turn off MBS Input dry contact Maintain bypass SAL Output dry contact Summary ala...

Page 20: ...vel 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the UPS is connected to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enable...

Page 21: ...lay Tower display 01 Output voltage setting Interface Settings Output voltage You may choose the following output voltage 208 output voltage is 208 Vac 220 output voltage is 220 Vac 230 output voltage...

Page 22: ...tput voltage is 208 Vac 220 output voltage is 220 Vac 230 output voltage is 230 Vac default 240 output voltage is 240 Vac 05 ECO voltage range settings Interface Settings Parameter 1 Set the acceptabl...

Page 23: ...1 is from 5 to 10 of the nominal voltage Default 5 07 Bypass enable disable when UPS is off Interface Settings Parameter 1 Enable or disable Bypass function You may choose the following two options E...

Page 24: ...settings Interface Settings Parameter 1 Set the acceptable high frequency point and low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high frequency point 51 0 54 0 Sets...

Page 25: ...ery Modules EBM are connected Allowed values are integer in the range 7 999 Ah The default value is 20 Ah Leave as default if connecting standard ABB External Battery Modules EBM This setting will ena...

Page 26: ...ce Settings Parameter 1 Clear EPO warning EPO active the UPS output is cut off To recover the normal status EPO connector must first be closed Enter this menu to clear the status of EPO The UPS will s...

Page 27: ...A D B A T T L O A D B A T T L O A D B A T T L O A D B A T T L O A D 27 4 OPER ATION 19 Ambient temperature warning enable disable Interface Settings Parameter 1 Set ambient temperature warning ENA Am...

Page 28: ...N Output receptacle 1 On default OFF Output receptacle 1 Off 25 Output receptacles 2 on off Interface Settings Parameter 1 Set output receptacle 2 ON Output receptacle 2 On default OFF Output receptac...

Page 29: ...5 0 7 5 1 0 0 L O A D H z 2 5 5 0 7 5 1 0 0 B A T T B A T T L L O A D 2 5 5 0 7 5 1 0 0 L O A D VAC 2 5 5 0 7 5 1 0 0 B A T T B A T T L L O A D 2 5 5 0 7 5 1 0 0 L O A D 2 5 5 0 7 5 1 0 0 B A T T B A...

Page 30: ...tery tray from the UPS and replace the batteries 5 Reinsert the battery tray with the replaced batteries back into the original location 6 Tightly secure the 4 screws to lock back the battery cover to...

Page 31: ...oad data and initiate shutdown of the equipment connected to the UPS NOTE CABLES LENGTHS SHALL NOT EXCEED 10 M KEEP ROUTING OF COMMUNICATION CABLES SEPARATED FROM MAINS SUPPLY AC AND DC CABLES 6 Commu...

Page 32: ...e USB port on a computer The EPO connector can be used to block the output of the UPS in case of an emergency The EPO connector can be configured as Normally Closed NC or Normally Opened NO through th...

Page 33: ...agement cards For more information contact your local supplier The PowerValue 11 RT G2 1 3 kVA is equipped with an intelligent slot for optional cards for remote management of the UPS through the Inte...

Page 34: ...ter soft start failure 11 X Inverter voltage high 12 X Inverter voltage Low 13 X Fault event Fault code Icon Inverter output short 14 X Battery voltage too high 27 X Battery voltage too low 28 X Over...

Page 35: ...PS output After repetitive overloads the UPS is locked in the bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart i...

Page 36: ...PowerValue 11 RT G2 1 3kVA www abb com ups ups sales ch abb com Copyright 2020 ABB All rights reserved Specifications subject to change without notice...

Reviews: