Alarm or Event
Possible cause
Remedy
UPS over temperature
Fault (Red) LED is On.
Beep continuous.
Code: F081
The UPS internal heat sink
temperature is too high, or a
fan has failed. At the warning
level, the UPS generates the
alarm but remains in the
current operating state. If
the temperature rises
another 2°C, the UPS
transfers to bypass mode or
standby mode.
Clear vents and remove any
heat sources. Allow the UPS
to cool. Ensure the airflow
around the UPS is not
restricted.
Restart the UPS. If the
condition persists, contact
your service representative.
ON Maintenance Bypass
Bypass (Orange) LED is on.
Code: A072
UPS was manually
commanded to switch to
bypass and will remain in
bypass until commanded out
of bypass.
Check the maintenance
bypass switch status.
In HE Mode
Line(green) LED is on.
Code: E063
The UPS is on bypass while
operating on the high
efficiency setting.
The equipment transferred
to bypass utility power as a
normal function of high
efficiency operation. Battery
mode is available and your
equipment is protected.
Site Wiring Fault
Fault (Red) LED is flash
1beep every 1 second
Code: A004
Site fault detection is
supported on all models any
time there is a grounding
neutral connection. Alarm
triggers when the difference
between ground and neutral
voltage is >15 V.
Site fault detection should be
enabled by default. It can still
be enabled / disabled from
the LCD settings menu.
Reconnect all input wires.
Back feed
Fault (Red) LED is On.
Beep continuous.
Code: F093
UPS has an unexpected
bypass current on battery
mode.
Transfer to maintenance
bypass and call service.
Inv Overload Fault
Fault (Red) LED is On
Beep continuous.
Code: F042
UPS has transferred to
bypass or fault mode
because of overload in
inverter mode.
The UPS transfers to battery
mode if supporting the load.
Remove some of the
equipment from the UPS.
Byp Overload Fault
Fault (Red) LED is On.
Beep continuous.
Code: F043
UPS has cut off the output
and transferred to fault
mode because of overload in
bypass mode or HE mode.
Remove some of the
equipment from the UPS.
Output Short Circuit
Fault (Red) LED is On.
Beep continuous.
Code: F031
Indicates that the UPS has
detected abnormally low
impedance placed on its
output and considers it a
short circuit.
Remove all the loads. Turn off
the UPS. Check if UPS output
and load has short circuit.
Ensure short circuit is
removed before turning on
again.
Fan Failure
Fault (Red) LED is flash
1 beep every 1 second
Code: A085
Indicates that the fan could
not work normally.
Check fans of UPS.
E
N
G
L
ISH
Summary of Contents for PowerValue 11 RT G2
Page 1: ... QUICK GUIDE PowerValue 11 RT G2 6 10 kVA ...
Page 3: ...DOCUMENT INFORMATION 3 01 02 ...
Page 4: ...4 03 04 ...
Page 5: ...DOCUMENT INFORMATION 5 10 11 12 2 4 5 6 7 8 9 1 3 14 11 15 13 05 06 07 ...
Page 6: ...6 ...
Page 8: ...8 ...
Page 38: ...38 POWERVALUE 11 RT G2 6 10 KVA KURZANLEITUNG D E U T S C H ...
Page 54: ...54 POWERVALUE 11 RT G2 6 10 KVA GUIDE DE RÉFÉRENCE R APIDE FR ANÇAIS ...
Page 70: ...70 POWERVALUE 11 RT G2 6 10 KVA GUIDA R APIDA I TA L I A N O ...
Page 86: ...86 POWERVALUE 11 RT G2 6 10 KVA GUÍA R ÁPIDA E S PA Ñ O L ...
Page 102: ...102 POWERVALUE 11 RT G2 6 10 KVA GUIA DE CONSULTA R ÁPIDA P O R T U G U Ê S ...
Page 118: ...118 POWERVALUE 11 RT G2 6 10 KVA PIK AOPAS S U O M I ...
Page 176: ...176 POWERVALUE 11 RT G2 6 10 КВ А КРАТКОЕ РУКОВОДСТВО Р У СС К И Й ...
Page 192: ...192 POWERVALUE 11 RT G2 6 10 KVA SKRÓCONY PODRĘCZNIK P O L S K I ...
Page 193: ... 速成指南 PowerValue 11 RT G2 6 10 kVA 重要安全须知 194 安装 199 操作 201 排故 203 中 文 ...
Page 222: ...222 POWERVALUE 11 RT G2 6 10 KVA Σ ΎΝΤΟΜΟΣ ΟΔΗΓΌΣ Ε Λ Λ Η Ν Ι Κ Ά ...