04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc
Page 15/29 ABB
Modifications reserved
3.7
Installation Checklist
All packing materials and restraints have been removed from the UPS cabinet.
The UPS system is placed in the installed location.
All conduits and cables are properly routed to the UPS.
All power cables are properly sized and terminated.
A ground conductor is properly installed.
If not using all wiring terminals, the provided protective covers are installed on the cabinet.
Battery cabinet installation instructions have been completed.
Air conditioning equipment is installed and operating properly.
The area around the installed UPS system is clean and dust-free. (It is recommended that the
UPS be installed on a level floor suitable for computer or electronic equipment.
Adequate workspace exists around the UPS.
Adequate lighting is provided around all UPS equipment.
Any optional accessories are mounted in their installed location and properly wired.
Start-up and operational checks have been performed by authorized service personnel.
3.8
Turning on the UPS
With utility power:
Press ON button continuously for more than 1 second to turn on the UPS. The UPS will function in
inverter mode and the LCD screen will indicate the UPS status.
Without utility power (Cold start)
If the utility power is not present, press ON button twice. The first time the button ON is pressed, the
UPS is powered. The second time the button ON is pressed for more than 1 second, the UPS is set to
inverter mode.
Note: By default the UPS automatic bypass is disabled.
If your mains supply is usually stable, enable the
bypass in the settings menu of the UPS (See section
Error! Reference source not found.
).
3.9
Battery test
Press the switch ON for more than 1 second to test if the battery is connected or if the battery is low.
This test can be done automatically and periodically according to the user configuration.
3.10
Turning off the UPS
From Inverter Mode
Press the OFF button continuously for more than 1 second to turn off the UPS. If the bypass mode is
disabled, the power is absent in the output. In case the bypass is enabled, the UPS will go into bypass
mode. Disconnect the utility power to remove the power from the output.
From Battery Mode
Press OFF button continuously for more than 1 second to turn off the UPS. Power will be then absent in
the output of the UPS.