7 TECHNICAL SPECIFICATIONS
GENERAL DATA
1 kVA
1 kVA B
2 kVA
2 kVA B
3 kVA
3 kVA B
Output rated power [W]
900 W
900 W
1800 W
1800 W
2700 W
2700 W
Output power factor
0.9
Topology
True online double conversion
Inbuilt batteries
Depending on the model
INPUT
Nominal input voltage
200 / 208 / 220 / 230 / 240 V
AC
Input voltage tolerance
110-300 V
AC
(depends on load level)
Input current THD
<5% with full resistive load
Frequency range
45-55 Hz / 54-66 Hz
Power factor
≥0.99
OUTPUT
Rated output voltage
200 / 208 / 220 / 230 / 240 V
AC
Voltage tolerance
(referred to 230V)
±2%
Voltage distortion
≤3% linear load, ≤5% non-linear load
Overload capability
(on inverter)
60s.: 105%-110% load / 30s.: 110%-125% load /
10s.: 125-150% load / 1s.: >150% load
Overload capability
(on bypass)
10m.: 125-150% load / 60s.: >150% load
Nominal frequency
50 or 60 Hz ± 0.2 Hz
Crest Factor
3:1
TRANFER TIME
Battery
inverter
0 ms
Bypass
inverter
< 4 ms
Inverter to Eco-mode
< 4 ms
Eco-mode to inverter
<10 ms
EFFICIENCY
AC-AC
≥
88%
In eco-mode
≥
93%
≥
94%
ENVIRONMENT
Protection rating
IP 20
UPS storage temperature
-15
– +60°C
Batteries storage
temperature
0~35°C
Operating temperature
0
– 45°C
Relative humidity
0-95% (Non-condensing)
Altitude
(above sea level)
<1000m for nominal power
BATTERIES
Type
VRLA, vented lead-acid
Battery configuration
-
3 x 7.2Ah
8 x 7.2Ah
8 x 7.2Ah
Backup time
-
> 5 minutes
> 9 minutes
> 5 minutes
Charging current
8A
1 A
8A
1 A
8A
1 A
Recharge time
-
3h to 90%
3h to 90%
3h to 90%
COMMUNICATIONS
User interface
LCD display
Communication cards
SNMP (option), AS400 relay card (option)
STANDARDS
Safety
IEC/EN 62040-1
Performance
IEC/EN 62040-3
ROHS
IEC/EN50581:2012
Manufacturing
ISO 9001:2008, ISO 14001:2004
WEIGHT, DIMENSIONS
Weight
7 kg
13 kg
13 kg
31 kg
13 kg
31 kg
Dimensions
WxHxD
145 x 220 x 400mm
192 x 347 x 460 mm
192 x 347 x 460 mm
*Technical specifications are subject to change without notice.
- De-rating to 90% when the output voltage is adjusted to 208VAC
- De-rating to 80% when the output voltage is adjusted to 200VAC
- De-rating to 60% when the UPS is in converter mode
- Over 1000 m the power de-rating is 1% every 100 m