11
USER M A N UA L
—
3. Installation
3 .1 Delivery, transportation,
positioning and storage
3 .1 .1 Receipt of the UPS and visual inspection
When receiving the UPS, carefully examine the
packing container and the UPS for any signs of
physical damage.
WARNING!
In case of recognizable damage:
do not connect any voltage to the
unit / Do not put the unit into
operation
The packing container of the UPS protects it from
mechanical and environmental damage.
To increase protection, the UPS is wrapped in a
plastic sheet. Keep the packaging for later re-use.
3 .1 .2 Unpacking list
After examining the package, open the box and
check the following items are included:
• 1 x PowerValue 11T UPS
• 1 X USB with complete documentation in
5 languages
• Multi-language quick installation guide
• 1 x India-IEC C13 cable (only for 1KB/1KS)
• 1 x India-IEC C19 cable
(only for 2KB/2KS/3KB/3KS)
• 1 x external battery cable (only for S models)
• 1 x USB cable
• 1 x fixing plate for battery cable
Examine the UPS for any signs of damage and
ensure that the received UPS corresponds to the
material indicated in the delivery note. Notify
your carrier or supplier immediately in case of
any damage.
3 .1 .3 Operation of UPS
The UPS system contains no user-serviceable
parts. If the battery service life (3~5 years at 25°C
ambient temperature) has been exceeded, the
batteries must be replaced. In this case, please
contact your dealer.
Be sure to deliver the spent battery
to a recycling facility or ship it to
your dealer in the replacement
battery packing material.
3 .1 .4 Storage of UPS
Before storing, charge the UPS 5 hours. Store the
UPS covered and upright in a cool, dry location.
During storage, recharge the battery in
accordance with the following table:
Storage
temperature!
Recharge
frequency
Charging
duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Summary of Contents for PowerValue 11T IN
Page 1: ... USER MANUAL PowerValue 11T IN 6 10 kVA ...
Page 2: ......