21
5 .3 .2 UPS shutdown
To shut down the UPS with mains supply:
1.
The LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be turning off to
bypass mode with beeping once. You could also enter the “control menu” to select the instruction
“Turn Off” to turn off the UPS. Please refer to the section of “LCD operation”;
NOTE
“TURN OFF” MEANS THAT UPS IS NOT WORKING ON LINE / CONVERTER / ECO / BATTERY / BATTERY TEST
MODE. SO EVEN THOUGH THE UPS IS TURNED OFF, IF INPUT OR BYPASS VOLTAGE IS NORMAL, THE
INTERNAL POWER SUPPLY WILL BE STILL WORKING; AND IF BYPASS STATUS HAS BEEN SET TO “ENABLE”,
THE OUTPUT VOLTAGE OF THE UPS WILL BE STILL EXIST
2. Disconnect the breakers, UPS will power off immediately. When UPS is shutdown, all the display and
fans will be turned off.