Modifications reserved
Page 17/50
4.3
Block diagram
Figure 12: Block diagram of PowerWave 33 S3. On the left with single input feed configuration and on the right with dual
input feed configuration.
4.4
Wiring
Before proceeding to wire the UPS, make sure that you have read and understood the chapter above
4.2 Electrical installation
and make sure that the following is respected:
•
The cable sections and fuse ratings are respecting the local standards. Alternatively, you can
use the recommended cable sections and fuse rating in the tables 6 and 7, which are according
to (IEC 60950-1).
Table 5: SINGLE INPUT FEED (CABLE LINKS TO ACHIEVE SINGLE INPUT ARE OPTIONAL)
Rated
output
power
Fuse A
Type:gL or
CB
(quantity x A)
Cable A
(quantity x
mm
2
)
Cable D
(quantity x
mm
2
)
Fuse E
Type:gR or
CB
(quantity x A)
Cable E
(quantity x mm
2
)
60 kW
3x100
5x(1x35)
5x(1x35)
2x160
2x(1x50)
80 kW
3x125
5x(1x50)
5x(1x50)
2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160
5x(1x70)
5x(1x70)
2x250
2x(1x120) or 2x(2x50) @ 42-45 batt.
blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200
5x(1x95)
5x(1x95)
2x300
2x(1x150) or 2x(2x50) @ 42-45 batt.
blocks
2x(1x120) or 2x(2x50) @ 46-50 batt.
blocks