Modifications reserved
Page 42/50
7
Maintenance
WARNING!
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED
BY A SERVICE ENGINEER FROM THE MANUFACTURER OR FROM AN
AGENT CERTIFIED BY THE MANUFACTURER..
7.1
User responsibilities
There are no parts within the UPS which need to be serviced by the user, so the maintenance
responsibilities of the user are zero. To maximize the useful working life and reliability of the UPS and
its batteries, the environment in which the UPS operates should be kept cool (20°C - 25°C), dry, dust
free and vibration free. The batteries should be hold fully charged.
7.2
Preventative maintenaince
The UPS system needs a regular and constant maintenance (preventative inspections) at least once a
year, even during the warranty period.
These preventative maintenance inspections are essential to ensure a correct functionality and
reliability of the UPS system. When the UPS is commissioned, the commissioning field service
engineer will attach a service record book to the front of the UPS and this will be used to record the
full service history of the UPS.
During a preventative maintenance the field service engineer might carry out some or all of following
checks:
•
Status and function check of UPS and batteries
•
UPS and batteries visual inspection (dust, mechanical damages, ..)
•
Visual inspection of screws and cable connections
•
Check of air ventilation and room temperature
•
Check the operation and function (commutations, remote monitoring and Signaling)
•
Current, voltage and frequencies measures
•
Measure and record the current load conditions
•
Check the load sharing (only in parallel systems)
•
Battery voltage check
•
Battery discharge test
•
Check transfer of the load from UPS to mains operation via static bypass
•
Unit cleaning
7.3
Deep battery test
The battery test takes approx. 3 minutes and should be performed only if:
•
there are no alarm conditions
•
the battery is fully charged
Summary of Contents for PowerWave 33 Series 3
Page 1: ... Copyright 2017 ABB All rights reserved User Manual PowerWave 33 Series 3 60 120 kW ...
Page 46: ...Modifications reserved Page 46 50 10 Attachments 10 1 Technical data sheet ...
Page 48: ......
Page 49: ... Copyright 2016 ABB All rights reserved Technical data sheet PowerWave 33 Serie 3 60 120 kW ...