Cable and fuse recommendations
Figure 3: block diagram PowerWave 33 S3 60-120kW
Cable Sections and fuse ratings recommended according to (IEC 60950-1).
Alternatively, local standards to be respected!
Table 4: SINGLE INPUT FEED (CABLE LINKS TO ACHIEVE SINGLE INPUT ARE OPTIONAL)
Rated
output
power
Fuse A
Type:gL or CB
(qty. x A)
Cable A
(qty. x mm
2
)
Cable D
(qty. x mm
2
)
Fuse E
Type:gR or CB
(qty. x A)
Cable E
(qty. x mm
2
)
60
kW
3x100
5x(1x35)
5x(1x35)
2x160
2x(1x50)
80
kW
3x125
5x(1x50)
5x(1x50)
2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160
5x(1x70)
5x(1x70)
2x250
2x(1x120) or 2x(2x50) @ 42-45
batt. blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200
5x(1x95)
5x(1x95)
2x300
2x(1x150) or 2x(2x50) @ 42-45
batt. blocks
2x(1x120) or 2x(2x50) @ 46-50
batt. blocks
Table 5: DUAL INPUT FEED (STANDARD VERSION)
Rated
output
power
Fuse B
Type:gL
or CB
(qty. x A)
Cable B
(qty. x
mm
2
)
Fuse C
Type:gL
or CB
(qty. x A)
Cable C
(qty. x
mm
2
)
Cable D
(qty. x
mm
2
)
Fuse E
Type:gR
or CB
Cable E
(qty. x mm
2
)
60
kW
3x100
5x35
3x100
5x35
5x35
2x160
2x(1x50)
80
kW
3x125
5x50
3x125
5x50
5x50
2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160
5x70
3x160
5x70
5x70
2x250
2x(1x120) or 2x(2x50) @ 42-45
batt. blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200
5x95
3x200
5x95
5x95
2x300
2x(1x150) or 2x(2x50) @ 42-45
batt. blocks
2x(1x120) or 2x(2x50) @ 46-50
batt. blocks