Safety
Most of the operator panels are fed with 24 V DC.
4
1
2
4
3
4
Power supply
230 V AC to 24 V DC
Power supply
230 V AC to 24 V DC
Power supply
230 V AC to 24 V DC
Operator panel
Operator panel
Operator panel
Distance?
Small controller with expansion unit
+24 V
+24 V
+24 V
0 V
0 V
0 V
230 V AC
COM1
COM100
Ch0
Ch1
Ch100
Ch101
5355
If a power supply that meets safety standards is used and only feeds the operator
panel, there is no problem. See 1 in drawing above.
However, if a 24 V unit that also feeds other units is used, there is reason to be
cautious, see 2 in drawing above. The operator panel does not have insulation
that meets safety requirements in the event of a potential short circuit between
230 V AC and 24 V DC. It is assumed that the 24 V feed is secure, for example,
SELV according to EN 60950 (protection against electric shock) and UL 950.
Here is an example that explains why a secure 24 V DC feed can be ruined
by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller
controller. Check that the clearances and creepage distances between 24 V DC
and 230 V AC fulfill EN 60950 or UL 950. If not, input a separate 24 V unit
into the operator panel.
40
3BSE069463-600 Rev D
Summary of Contents for PP885
Page 1: ...Compact Product Suite Panel 800 Version 6 PP885 Hardware and Installation ...
Page 2: ......
Page 3: ...Panel 800 Version 6 PP885 Hardware and Installation ...
Page 6: ...6 3BSE069463 600 Rev D ...
Page 16: ...Appearance of Air in Touch Screen Section 2 Safety Precautions 16 3BSE069463 600 Rev D ...
Page 24: ...Section 4 Technical Data 24 3BSE069463 600 Rev D ...
Page 32: ...PP885 Outline Section 6 Operator Panel Drawings 32 3BSE069463 600 Rev D ...