PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
5
1. Safety instructions
These safety instructions are intended for all work on the PQFA.
Neglecting these instructions can cause physical injury and death.
All electrical installation and maintenance work on the PQFA should be
carried out by qualified electricians.
Do not attempt to work on a powered PQFA.
After switching off the mains, always wait at least 5 minutes before
working on the unit in order to allow the discharge of DC capacitors
through the discharge resistors.
DC capacitors might be charged to more than 1000V.
Before manipulating current transformers, make sure that the secondary
is short-circuited. Never open the secondary of a loaded current
transformer.
You must always wear isolating gloves and eye-protection when
working on electrical installation. Also make sure that all local safety
regulations are fulfilled.
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...