120 The PQF-Manager user interface
Manual Power Quality Filter PQFS
7.9.3.2
Setting up the ‘auto restart’ function
For setting up the ‘auto restart’ function, go to [/Welcome/Settings/Installation
set./Start-Stop set.].
In multi-master units these functions need to be set up in each master-unit in order to
obtain full redundancy.
The ‘auto restart’ function when enabled ensures that the filter restarts automatically
after a power outage if the filter was on before the power outage occurs. A time delay
can be programmed to define how long after the power returns, the filter will restart.
When the ‘auto restart’ function is disabled, the filter will not restart automatically after
a power outage.
−
To enable/disable the ‘auto restart’ function, go to
[/Welcome/Settings/Installation set./Start-Stop set./] and enable” the auto
start option.
−
To program the delay after which the filter has restart once the power returns, in
the same menu specify the desired delay. This delay in available from the “drop –
down” menu, in “seconds”.
Remark: By default the ‘auto restart’ function is enabled and the delay time is set at 15s.
7.9.3.3
Setting up the system clock
For setting up the system clock, go to [/Welcome/Settings/Installation set./Clock]
In multi-master units these functions need to be set up in each master-unit in order to
obtain full redundancy.