USER I N T ER FAC E | I N S TA L L AT I O N
19
—
Table 13: Ambient conditions for operation and storage
Name
Storage
Operation
Altitude
Nominal output at 0 to 1000 m
(3300 ft) above sea level
Temperature
-25 to 70°C (-13 to 158°F)
-10 to 40°C (23°F to 104°F)
(a)
Relative humidity
Max. 85%
Max. 95% non-condensing
Contamination levels (IEC 60721-3-3)
Chemical class 3C3
Chemical class 3C1
(b)
Mechanical class 3S3
Mechanical class 3S1
(c)
—
04 Installation
4.1 Upon reception
Before installing the PQstorI make sure that:
•
The packaging used for delivery is in
good condition
•
There are no signs of transportation damage
•
Your package also contains a communication
cable to operate modules in parallel
Notify any loss or damage to these items
immediately to your ABB representative.
4.2 Location
Make sure that you transport, store and operate
the product within the range of temperature,
(a)
Up to 50°C (122°F) with auto-derating
(b)
Locations with normal levels of contaminants, experienced in urban areas with scattered industrial
activity or heavy traffic.
(c)
Locations with no special precautions taken to minimize the presence of sand or dust.
The product weighs approximately 20 kilograms and can be lifted by hand by two people. It must be
installed indoors under IP20 standard protection class when fitted in cabinets. Its operation emits
below 61 dBA of noise at one meter of the module.
humidity and environmental contaminants set
out in Table 13. Install the module in a location
free of conductive dust that may damage the
equipment.
4.3 Identification tag
Each PQstorI is fitted with identification
nameplates on its front panel detailing the
product model, nominal voltage range, network
frequency, serial number and ABB internal article
code.