Program features 17
Country settings
Preset country codes
The PRO-33.0-TL inverter has a country code table with preset grid code settings for 37
countries. The installation country is initially set with the First start assistant or with the
parameter
The First start assistant activates automatically when the inverter is turned on for the very
first time. See more details in the
PRO-33.0-TL Product manual
. The country code may
also have separate options for low voltage and medium voltage settings when there are
separate requirements for MV connection in the same country, such as Germany LV and
Germany MV. If the country code is not set, the inverter does not operate.
When a country code is selected, all the necessary parameter settings are set to match
the country requirements. The country code settings affects the parameters in the groups
,
and
. The parameters include, for example, nominal output values, tripping limits for
under- and overvoltage and under- and overfrequency, initial connection delays, variety of
reconnection delays, anti-islanding settings, reactive power settings, fault ride-through
settings, power limitation settings and MPPT recovery settings. Usually the country code is
not changed during the lifetime of the inverter.
You can change the country code with parameter
Note
: Changing this value will always override any changes made in the above-mentioned
parameter groups.
When a country code is initially set, all the preset parameters can be modified if they
adhere to the local grid code requirements. See details in chapter
on page
.
Settings
Diagnostics
Customizing country code settings
If the country code-related parameter settings (parameters in groups
,
to be changed, follow this procedure:
Disable the inverter
1. Enter the
Service
menu.
2. Select
Inverter operation
and press
Edit
.
3. Change the value from
Enable
to
Disable
and press
Save
. After a short period, the
inverter stops running and it is possible to change the parameter values.
Customize settings
1. Enter the parameter list:
Service menu
-
Parameters
-
Complete list
.
2. Check that you have a country code set with parameter
3. Make required changes to the parameters.
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...