66 Parameters
Any message
Timeout counter is reset when any Modbus TCP
register is accessed.
1
Ctrl write
Timeout counter is reset when the control word
register or reference register REF1/REF2 are
written to.
For more information, see
FENA-11/21 manual
.
2
Auto
Auto negotiate
0
151.22
Word order
(
is
FENA-11/-21.
)
Selects the order in which 16-bit registers of 32-
bit parameters are transferred. For each register
(16-bit), the first byte contains the high order byte
and the last byte contains the low order byte.
HiLo
LoHi
The first register contains the low order word and
the second register contains the high order word.
0
HiLo
The first register contains the high order word and
the second register contains the low order word.
1
151.23
Address mode
(
is
FENA-11/-21.
)
Defines the mapping between inverter
parameters and Modbus holding registers.
Note
: Changes are effective only when settings
are refreshed or the device is power cycled.
Mode 0
Mode 0
Both 16 bit and 32 bit access is possible for
parameter groups 101...199, indexes 1...99.
RegisterAddress for 16bit access =
100*Para ParamIndex.
RegisterAddress for 32bit access = 20000 +
200*Para 2*ParamIndex.
0
Mode 1
Only 16 bit access possible, parameter groups
1... 255, indexes 1... 255.
RegisterAddress = 256*Para
ParamIndex.
Note. This mode does not allow access to 32-bit
parameter values.
1
Mode 2
Only 32 bit access possible, parameter groups
1…127, indexes 1... 255.
RegisterAddress = 512*Para
2*ParamIndex.
2
Mode 3
Only 32 bit access possible, parameter groups
1…255, indexes 1... 127.
RegisterAddress = 256*Para
2*ParamIndex.
3
151.23
Init status
(
is
FSCA-01.
)
Status of adapter module (internal use)
0
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...