Parameters 73
158.12
CRC errors
Contains the count of CRC error messages
received by the device. This is an indicator of
noise on the RS485 bus.
0
0 … 4 294 967 295
- / 1 = 1
158.17
Transmit delay
Defines a minimum response delay in addition to
any fixed delay imposed by the protocol.
Note
: Changes are effective only when settings
are refreshed or the device is power cycled.
0
158.33
Addressing mode
Defines the mapping between parameters and
holding registers in the upper Modbus register
range (101... 65536).
Note
: Changes are effective only when settings
are refreshed or the device is power cycled.
7
Mode 1
Only 16bit access is possible for parameter
groups 1... 255, indexes 1... 255.
RegisterAddress = 256*Para
ParamIndex.
Note
: This mode does not allow access to 32-bit
parameter values.
1
Mode 6
Both 16bit and 32bit access is possible for
parameter groups 101... 199, indexes 1... 99.
RegisterAddress for 16bit access =
100*(ParamGroup - 100) + ParamIndex.
RegisterAddress for 32bit access = 20000 +
200*(ParamGroup - 100) + 2*ParamIndex.
6
Mode 7
Only 32bit access is possible for parameter
groups 101... 227, indexes 1... 255.
RegisterAddress = 512*(ParamGroup - 100) +
2*ParamIndex.
Note
: Only this mode can access all parameter
values.
7
158.34
Word order
Selects the order in which 16-bit registers of 32-
bit parameters are transferred.
Note
: Changes are effective only when settings
are refreshed or the device is power cycled.
LO-HI
HI-LO
First register contains high order word and
second register contains low order word.
0
LO-HI
First register contains low order word and second
register contains high order word.
1
158.101
Data I/O 1
Selects and maps any internal parameter of the
inverter to Modbus RTU holding register address
0. Allows the user to define/redefine the mapping
scheme that can suit the required Modbus RTU
master.
See the parameters list and mappings in chapter
Product name and serial number
.
-
...
...
...
...
158.169
Data I/O 69
-
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...