90 Parameters
188.21
Connect underfrequency
limit
Sets limit that is used only on connecting to the
grid. When the inverter is connected, this limit is
disabled. See parameter
-2 Hz
-
1 = 1 Hz /
100 = 1 Hz
188.22
Connect overfrequency
type
Selects connection type for overfrequency
protection.
Disabled
Disabled
Limit is disabled.
0
Disconnected
Limit is enabled when the inverter is disconnected
from the grid.
1
Reconnection
Limit is enabled when inverter trips to
overfrequency.
2
188.23
Connect overfrequency
limit
Sets limit that is used only on connecting to the
grid. When the inverter is connected, this limit is
disabled. See parameter
2 Hz
-
1 = 1 Hz /
100 = 1 Hz
188.24
Connect undervoltage type Defines how
behaves.
• When enabled, grid connection is allowed only
when grid voltage is above the limit.
• When disabled, limit is not checked.
Disable
Disable
0
Enable
1
188.25
Connect undervoltage limit Sets the limit that is used only when the inverter is
not connected. The limit is disabled when the
inverter is connected. The purpose is to allow
different connect and disconnect limits. See
parameter
.
80
-
1 = 1
188.26
Connect overvoltage type
Defines how
behaves.
• When enabled, grid connection is allowed only
when grid voltage is above the limit.
• When disabled, limit is not checked.
Disable
Disable
0
Enable
1
188.27
Connect overvoltage limit
Sets the limit used only when the inverter is not
connected. The limit is disabled when the inverter
is connected. The purpose is to allow different
connect and disconnect limits. See parameter
.
120
-
1 = 1
188.30
Underfrequency enable 1
Enables underfrequency protection.
1
0 ... 1
1 = 1
188.31
Underfrequency limit 1
Sets limit for underfrequency protection.
-1 Hz
-30 ... 0 Hz
1 = 1 Hz /
10 = 1 Hz
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...