Parameters 53
-
1 = 1 /
10 = 1
124.30
Q(x) curve
Selects the input signal used in Q(x) regulation
curve.
-
Q(U)
Input: Measured grid voltage
Output: Reactive power reference
0
Q(P)
Input: Actual active power
Output: Reactive power reference
1
CosPhi(P)
Input: Actual active power
Output: CosPhi
2
124.31
Lock-in level
Defines the lock-in level to activate the Q(x)
regulation curve.
20%
0 … 200%
1 = 1%
124.32
Lock-out level
Defines the lock-out level to deactivate the Q(x)
regulation curve.
5%
0 … 200%
1 = 1%
124.33
Q(x) input level 1
Defines the first input value for the Q(x) regulation
curve. When the selected input signal reaches
this value, reactive power reference is set to the
value defined by parameter
.
0%
-
1 = 1% /
100 = 1%
...
...
...
...
124.38
Q(x) input level 6
See parameter
124.39
Q(x) output level 1
Defines the first reference output value for the
Q(x) regulation curve. When the selected input
signal reaches
, the
reactive power reference is set to the value
defined by this parameter.
0
-
1 = 1 /
100 = 1
...
...
...
...
124.44
Q(x) output level 6
See parameter
124.45
Q(U) activation delay
Defines the activation delay for Q(U) curve.
0 ms
0...30000 ms
Time
1 = 1 ms
124.46
Q(U) activation level low
Defines the lower activation level for Q(U) curve.
100%
0...200%
Activation level
1 = 1%
124.47
Q(U) activation level high
Defines the higher activation level for Q(U) curve. 100%
0...200%
Activation level
1 = 1%
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...