56 Parameters
130.81
P(U) release ramp
Sets the ramp up after power limit release.
20%/min
0 … 100%/min
1 = 1%/min
130.90
Flat-top limit
Sets the active power limit which cuts the semi-
circular operating range to a flat-top range.
200%
0 … 200%
1 = 1%
130.92
Active power ramping
Enables the active power ramping function.
Disable
Disable
0
Enable
1
130.93
Active power ramp
Sets the active power ramp rate.
100%/min
0 … 1000%/min
1 = 1%/min
130.94
Shut down ramp
Sets the active power ramp that is applied in a
controlled shut down.
100%/s
0 … 1000%/s
1 = 1%/s
130.98
External limit ramp up
Sets the ramp up time for
.
0 ms
0 … 60 000 ms
1 = 1 ms
130.99
External limit ramp down
Sets the ramp down time for
0 ms
0 … 60 000 ms
1 = 1 ms
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)